| Ordering details | |
| Product type description | SRB 031LC-0,6SEC |
| Article number | |
| EAN code | |
| eCl@ss | 27-37-19-01 |
| Approval | |
| Approval |
BG
USA/CAN |
| Classification | |
| Standards | EN ISO 13849-1, IEC 61508, EN 60947-5-1 |
| PL | bis d (STOP 1) |
| Control category | up 3 (STOP 1) |
| DC | > 60% (STOP 1) |
| CCF | > 65 points |
| PFH value | 5.0 x 10-9/h |
| SIL | bis 3 (STOP 0)up 3 (STOP 1) |
| Mission time | 20 Years |
| Global Properties | |
| Product name | SRB 031LC-0,6SEC |
| Standards | IEC/EN 60204-1, EN 60947-5-1, EN ISO 13849-1, IEC 61508 |
| Compliance with the Directives (Y/N)
| Yes |
| Climatic stress | EN 60068-2-78 |
| Mounting | snaps onto standard DIN rail to EN 60715 |
| Terminal designations | IEC/EN 60947-1 |
| Materials | |
| - Material of the housings | Plastic, glass-fibre reinforced thermoplastic, ventilated |
| - Material of the contacts | , Ag-Ni, self-cleaning, positive action |
| Weight | 230 g |
| Start conditions | Automatic or Start button (Optional monitored) |
| Start input (Y/N) | Yes |
| Feedback circuit (Y/N) | Yes |
| Start-up test (Y/N) | No |
| Automatic reset function (Y/N) | Yes |
| Reset with edge detection (Y/N) | No |
| Pull-in delay | |
| - ON delay with automatic start | ≤ 30 ms |
| Drop-out delay | |
| - Drop-out delay in case of power failure | delay time ±30% at 24 VDC and Duty cycle > 3.5 s |
| - Drop-out delay in case of emergency stop | delay time ± 30% |
| delay time | 600 ms |
| Mechanical data | |
| Connection type | Screw connection |
| Cable section | |
| - Min. Cable section | 0,25 mm² |
| - Max. Cable section | 2.5 mm² |
| Pre-wired cable | rigid or flexible |
| Tightening torque for the terminals | 0,6 Nm |
| Detachable terminals (Y/N) | No |
| Mechanical life | 10.000.000 operations |
| Electrical lifetime | Derating curve available on request |
| restistance to shock | 10 g / 11 ms |
| Resistance to vibration To EN 60068-2-6 | 10...55 Hz, Amplitude 0,35 mm, ± 15 % |
| Ambient conditions | |
| Ambient temperature | |
| - Min. environmental temperature | −25 °C |
| - Max. environmental temperature | +45 °C |
| Storage and transport temperature | |
| - Min. Storage and transport temperature | −40 °C |
| - Max. Storage and transport temperature | +85 °C |
| Protection class | |
| - Protection class-Enclosure | IP40 |
| - Protection class-Terminals | IP20 |
| - Protection class-Clearance | IP54 |
| Air clearances and creepage distances To IEC/EN 60664-1 | |
| - Rated impulse withstand voltage Uimp | 4 kV |
| - Overvoltage category | II To VDE 0110 |
| - Degree of pollution | 2 To VDE 0110 |
| Electromagnetic compatibility (EMC) | |
| EMC rating | conforming to EMC Directive |
| Electrical data | |
| Rated DC voltage for controls | |
| - Min. rated DC voltage for controls | 20.4 VDC |
| - Max. rated DC voltage for controls | 28.8 VDC |
| Rated AC voltage for controls, 50 Hz | |
| - Min. rated AC voltage for controls, 50 Hz | - |
| - Max. rated AC voltage for controls, 50 Hz | - |
| Rated AC voltage for controls, 60 Hz | |
| - Min. rated AC voltage for controls, 60 Hz | - |
| - Max. rated AC voltage for controls, 60 Hz | - |
| Contact resistance | max. 100 mΩ |
| Power consumption | 1.7 W; 1.9 VA, plus signalling output |
| Type of actuation | DC |
| Rated operating voltage Ue | 24 VDC |
| Electronic protection (Y/N) | No |
| Fuse rating for the operating voltage | 1.25 A (5 x 20 mm) slow blow |
| Inputs | |
| Monitored inputs | |
| - Short-circuit recognition (Y/N) | No |
| - Wire breakage detection (Y/N) | Yes |
| - Earth connection detection (Y/N) | Yes |
| Number of shutters | 0 piece |
| Number of openers | 2 piece |
| Cable length | 1500 m with 1.5 mm²;2500 m with 2.5 mm² (for Rated voltage) |
| Conduction resistance | max. 40 Ω |
| Outputs | |
| Stop category | 1 |
| Number of safety contacts | 3 piece |
| Number of auxiliary contacts | 1 piece |
| Number of signalling outputs | 0 piece |
| Switching capacity | |
| - Switching capacity of the safety contacts | max. 230 VAC, 6 A ohmic (inductive in case of appropriate protective wiring) |
| - Switching capacity of the auxiliary contacts | 24 VDC, 2 A |
| Fuse rating | |
| - Protection of the safety contacts | 6 A gG D-fuse |
| - Fuse rating for the auxiliary contacts | 2 A slow blow |
| Utilisation category To EN 60947-5-1 | AC-15: 230 V / 6 ADC-13: 24 V / 6 A |
| Number of undelayed semi-conductor outputs with signaling function | 0 piece |
| Number of undelayed outputs with signaling function (with contact) | 0 piece |
| Number of delayed semi-conductor outputs with signaling function. | 0 piece |
| Number of delayed outputs with signalling function (with contact). | 1 piece |
| Number of secure undelayed semi-conductor outputs with signaling function | 0 piece |
| Number of secure, undelayed outputs with signaling function, with contact. | 0 piece |
| Number of secure, delayed semi-conductor outputs with signaling function | 0 piece |
| Number of secure, delayed outputs with signaling function (with contact). | 3 piece |
| LED switching conditions display | |
| LED switching conditions display (Y/N) | Yes |
| Number of LED´s | 4 piece |
| LED switching conditions display | |
| - The integrated LEDs indicate the following operating states. | |
| - Position relay K2 | |
| - Position relay K1 | |
| Supply voltage UB | |
| - Internal operating voltage Ui | |
| Miscellaneous data | |
| Applications |
Emergency-Stop button
Pull-wire emergency stop switches
Guard system |
| Dimensions | |
| Dimensions | |
| - Width | 22.5 mm |
| - Height | 100 mm |
| - Depth | 121 mm |
| notice | |
| Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. | |
| notice - Wiring example | |
| Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R) and feedback circuit (H2). | |
| The control system recognises wire-breakage and earth faults in the monitoring circuit. | |
| Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. | |
| Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals X1/X2. If the feedback circuit is not required, establish a bridge | |
| The wiring diagram is shown with guard doors closed and in de-energised condition. | |
| K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 WuppertalThe data and values have been checked throroughly. Technical modifications and errors excepted.Generiert am 12.03.2017 - 16:34:37h Kasbase 3.2.6.F.64I | |